Question #6 (Topic: )
Refer to the exhibit.
[Cisco-200-601-6.0/Cisco-200-601-5_2.png]
All of the vlans listed in the routing table below are trunked using 802.1q and are active on
all switches. PLC1, PLC2, and PLC3 each has IP address 192.168.0.1/24 and are
connected to ports configured for vlan 50. L2SW1, L2SW2, and L2SW3 are not using vlan
trunking for vlan 50.
L3SW1 has following routing table:
10.0.0.0/8 is variably subnetted, 12 subnets, 2 masks
C 10.3.138.0/23 is directly connected, Vlan307
C 10.3.136.0/23 is directly connected, Vlan306
C 10.15.153.0/24 is directly connected, Vlan398
C 10.3.142.0/23 is directly connected, Vlan309
C 10.3.140.0/23 is directly connected, Vlan308
C 10.3.186.0/23 is directly connected, Vlan293
C 10.15.154.0/24 is directly connected, Vlan399
C 10.3.184.0/23 is directly connected, Vlan292
C 10.3.190.0/23 is directly connected, Vlan295
C 10.3.188.0/23 is directly connected, Vlan294
C 10.3.182.0/23 is directly connected, Vlan291
C 10.3.180.0/23 is directly connected, Vlan290
PLC1, PLC2, and PLC3 cannot be reconfigured. What can be done to be able to
simultaneously communicate with PLC1, PLC2, and PLC3?
[Cisco-200-601-6.0/Cisco-200-601-5_2.png]
All of the vlans listed in the routing table below are trunked using 802.1q and are active on
all switches. PLC1, PLC2, and PLC3 each has IP address 192.168.0.1/24 and are
connected to ports configured for vlan 50. L2SW1, L2SW2, and L2SW3 are not using vlan
trunking for vlan 50.
L3SW1 has following routing table:
10.0.0.0/8 is variably subnetted, 12 subnets, 2 masks
C 10.3.138.0/23 is directly connected, Vlan307
C 10.3.136.0/23 is directly connected, Vlan306
C 10.15.153.0/24 is directly connected, Vlan398
C 10.3.142.0/23 is directly connected, Vlan309
C 10.3.140.0/23 is directly connected, Vlan308
C 10.3.186.0/23 is directly connected, Vlan293
C 10.15.154.0/24 is directly connected, Vlan399
C 10.3.184.0/23 is directly connected, Vlan292
C 10.3.190.0/23 is directly connected, Vlan295
C 10.3.188.0/23 is directly connected, Vlan294
C 10.3.182.0/23 is directly connected, Vlan291
C 10.3.180.0/23 is directly connected, Vlan290
PLC1, PLC2, and PLC3 cannot be reconfigured. What can be done to be able to
simultaneously communicate with PLC1, PLC2, and PLC3?
A. Enable NAT on L3SW1
B. Enable NAT on L2SW1 – L2SW3
C. Enable NAT on L2SW4
D. Add vlan 50 to L2SW4 and assign the administrator's an IP address on 192.168.0.0/24 network
Answer: B
Question #7 (Topic: )
Profinet has been disabled on a Cisco Industrial Ethernet switch, which CLI commands
correctly enable ProfiNET on VLAN 10?
correctly enable ProfiNET on VLAN 10?
A. switch(config)#profinet switch(config)#profinet vlan 10
B. switch#enable profinet switch(config)#profinet vlan 10
C. switch(config)#profinet switch(config)#vlan 10 switch(config-vlan)#profinet
D. switch#enable profinet switch(config)#vlan 10 switch(config-vlan)#profinet
Answer: A
Question #8 (Topic: )
A ProfiNET management system operator is unable to see diagnostic information for a
Cisco Industrial Ethernet switch that has been added to a SIMATIC management station.
Based on the provided CLI output, which statement is correct?
switch# show profinet status
State : Enabled
Vlan : 201
Id : IE2000-Switch
Connected : Yes
ReductRatio : 128
GSD version : Mis-match
Cisco Industrial Ethernet switch that has been added to a SIMATIC management station.
Based on the provided CLI output, which statement is correct?
switch# show profinet status
State : Enabled
Vlan : 201
Id : IE2000-Switch
Connected : Yes
ReductRatio : 128
GSD version : Mis-match
A. The assigned ProfiNET VLAN is not valid and should be less than 100
B. LLDP has been disabled on this switch
C. The GSD file version on the switch does not match the GSD file version on the management station
D. The Reduction Ration has been set too low
Answer: C
Question #9 (Topic: )
A shutdown in the cookie cutter machine was traced to a broken network cable. What are
two reasons that explain why using DLR is an appropriate choice for network resiliency?
(Choose two)
two reasons that explain why using DLR is an appropriate choice for network resiliency?
(Choose two)
A. DLR is designed for single network operation at the machine level
B. Moving to a linear topology will reduce the number of cables and so reduce risk of cable failure
C. DLR is the only resiliency technology that is supported by CIP Safety
D. Layer 2 resiliency protocols like REP and RSTP do not have a fast enough convergence time for motion control
E. Half of the network traffic goes clockwise on the ring and the other half counter- clockwise, reducing by 50% the impact of cable failure
Answer: A,D
Question #10 (Topic: )
Which scenario represents the correct configuration to support the SSIDs of this
autonomous access point?
autonomous access point?
A.
B.
C.
D.
Answer: D